6ES7417-4HT14-0AB0 產(chǎn)品報(bào)價(jià):
6es7417-4ht14-0ab0 cpu417-4h; 冗余熱備cpu 30 mb ram
上海勵(lì)輝自動(dòng)化科技有限公司
聯(lián) 系 人 : 熊彬 ()
銷(xiāo) 售 直 線:
傳 真:
聯(lián) 系 :
24小時(shí)手機(jī) :
上海勵(lì)輝誠(chéng)信銷(xiāo)售西門(mén)子 可編程控制器,人機(jī)界面,數(shù)控伺服,變頻器 ,伺服電機(jī),工業(yè)以太網(wǎng)
,在價(jià)格上有較大優(yōu)勢(shì),更注重售后服務(wù),上海勵(lì)輝竭誠(chéng)為您服務(wù),歡迎您!
6es7417-4ht14-0ab0
6es7417-4xt05-0ab0
simatic s7-400,cpu 417-4 *處理單元,帶: 30 mb 工作內(nèi)存, (15 mb代碼;15 mb數(shù)據(jù)) 1個(gè)接口 mpi 12 mbit/s, ,2個(gè)接口 profibus dp, 3./4. if ifm模塊,可插拔
the cpu 417-4 has:
- powerful processor:
the cpu achieves instruction execution times as low as 0.018 µs per binary instruction. - 30 mb ram (of which 15 mb each for program and data);
fast ram for parts of the user program relevant to execution. - flexible expansion:
up to 262144 digital and 16384 analog inputs/outputs. - multi-point interface mpi:
with the mpi it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 mbit/s. the cpu can establish up to 44 connections to stations of the communications bus (c bus) and the mpi.
note:
if the profibus dp interface and mpi interface are operated simultaneously, it is only possible to connect the following bus connector to the mpi interface: - with socket: 6es7 972-0bb41-0xa0
- without socket: 6es7 972-0ba41-0xa0
- mode selector switch:
designed as toggle switch. - diagnostics buffer:
the last 120 fault and interrupt events are retained in a ring buffer for diagnostic purposes (extendable). - real-time clock:
the date and time are appended to diagnostic messages of the cpu. - memory card:
for expansion of the integrated load memory. the information in the load memory comprises s7-400 parameterization data in addition to the program and therefore requires twice as much memory space. the result is: - the integral load memory is not sufficient for large programs, therefore a memory card is frequently required.
ram and feprom cards (feprom for retentive storage) are available
- profibus dp interface:
the profibus dp master interface allows a distributed automation configuration offering high speed and ease of use. from the user's point of view, the distributed i/o is treated as central i/o (same configuring, addressing, and programming).
mixed configuration: simatic s5 with simatic s7 as profibus master to en 50170.
note:
if the profibus dp and mpi interface are operated simultaneously, it is only possible to connect the following bus connectors to the mpi interface: - with socket: 6es7 972-0bb41-0xa0
- without socket: 6es7 972-0ba41-0xa0
- two additional slots:
two additional profibus dp master systems can be connected via if 964-dp interface modules.
functions
- block protection:
a password concept also protects the user program from unauthorized access - integrated hmi services:
the user only has to specify the source and destination of the data with hmi devices. the data are then transported cyclically and automatically by the system. - integrated communication functions:
- pg/op communication
- global data communication
- s7 standard communication
- s7 communication
configurable attributes
the step 7 tool "hardware configuration" can be used to program the properties and response of the s7-400 including the cpus, e.g.
- multipoint interface mpi:
- definition of node addresses
- startup/cycle behavior
- stipulation of the maximum cycle time and communication load
- address allocation:
addressing of i/o modules - retentive area:
definition of the number of retentive bit memories, counters, timers, data blocks, and clock memories - size of the process image, local data
- length of the diagnostics buffer
- protection level:
definition of access authorizations to program and data - system diagnostics:
definition of the handling and scope of diagnostics messages - timed interrupts:
setting of periods - configuring