Single core cable armored problems caused by this website are mentioned in many parts of the single core cable cannot be used for armored AC lines and frequent start and stop of the DC line, why? According to the principle of electromagnetic conversion, when the conductor steel tape armoured single core cable through alternating current (frequent start stop equivalent to alternating current), there is a armouring steel strip has good permeability properties, formation of eddy current in the strip (similar in principle of intermediate frequency furnace), make steel produce high temperature heating. In a very short period of time, resulting in the cable insulation layer to melt or accelerate the aging, insulation damage, resulting in the cable breakdown. If one has no end of steel have a good grounding, because every circle between the strip does not guarantee good contact resistance and the strip itself, and the conductor strip may form a "current transformer, electric potential in some range will have a higher risk. According to the law of conservation of energy, steel strip heating to consume electric energy, will increase the voltage drop on the cable, and then the use of electrical equipment can not normally start, or even damage. Because have some areas must use the armoured cable, can have effectively solve the problems in the environment, such as pest etc.. How to deal with it? You can use steel wire armored cable, aluminum, stainless steel tape armoured cable armored cable or directly using the Armored Core (single) cable.JHXG電機引接線
One case: We assist customers in production by other manufacturers at least four single core steel armored cable accident - cable, short length, the failure time of about 3 to 5 years; the fault phenomenon is breakdown.
案例二: 我們協(xié)助客戶處理至少一次單芯鋼帶鎧裝電纜事故——電纜是由其他 廠家生產(chǎn),長度約 500 米,故障現(xiàn)象先有有有有 N 線擊穿,更換后,電機不能啟 動,線路壓降大;建議客戶改用 3+2 電纜,問題解決。
Case two: We assist customers in production by other manufacturers at least one single core cable steel armored cable accident -- is about 500 meters in length, the first fault phenomenon ft-21-1 N line breakdown, after the replacement, the motor will not start, line drop; recommend customers to switch to the 3+2 cable, to solve the problem.
Analysis: the case is visible, using steel armored cable on the line, at least will shorten the service life of the cable. The cause of steel tape armoured single core cable is: because the buyer understanding of design drawings on cable model errors, and subjective change specifications. When the steel tape armoured single core cable in the short length, the actual current flow through the much smaller than the maximum load of cable, cable life in discount; when the maximum load flow length or current near the cable fault, immediay. Approach of procurement, design specifications can be written as. In the line and frequent start stop in the DC line, do not use steel tape armoured single core cable, not the nonmagnetic armour single core cable laying alone in magnetic ducts. If there is a single conductor around closed ferromagnetic materials, alternating magnetic field through the alternating current will produce eddy current problems in ferromagnetic materials. Multi core cable due to the inflow and outflow of current equal (normal operation), there is no electromagnetic induction problem. The problem will cause eddy current protection device, cable line loss decreased sensitivity to fever, increased, shortened life expectancy, may lead to serious fires. If the need for single core armored cable communication system, can be made of stainless steel, copper, Aluminum Alloy and other non ferromagnetic armour material or take measures to prevent eddy current strip. Similarly, the single core cable should be avoided to wear a steel pipe and the use of closed iron and magnetic materials, such as cable clamp. Single core armored power cable has great limitation in use, is not reasonable in structure, concrete analysis is as follows.
By "electromagnetism" shows that when steel tape armoured single core cable during normal operation, the conductor through alternating current (very frequent start stop cable lines is also equivalent to the alternating current), so around the cable will produce alternating electromagnetic field greatly, and armored steel has good magnetic conductivity, in operation in the main, secondary coil strip and the conductor is similar to the current transformer, when alternating electromagnetic field across the strip, will be induced by alternating current, and the strip itself has a relatively large resistance, caused by self heating, thereby forming eddy current loss and hysteresis loss in the steel belt, so in a very short period of time, strip it will produce high temperature, plus the conductor in normal operation of the heat, if the heat can not be distributed in a timely manner (such as laying underground, etc.) can lead to electric The insulation layer of the cable is melted or accelerated aging, and the insulation performance of the cable is damaged, which leads to the breakdown of the cable or the failure of the cable in advance.
At present, there are many domestic enterprises to adopt steel wire armored plus wire isolation structure on single core cables, actually this kind of "magnetic" structure is not reasonable, the magnetic isolation structure is intended to increase the reluctance of the magnetic circuit, the magnetic induction intensity decreases in wire, thereby reducing wire loss, but in the actual operation, the lines of force distortion caused by copper wire only, without interrupting the magnetic field lines, that is to say and can not achieve the purpose of increasing reluctance, the concrete analysis for Shanghai Electric Cable Research Institute senior expert Professor Ma Guodong in the "on" single core wire armoured power cable and cable ampacity "works". In the "cable ampacity" Professor Ma Guodong a book through a lot of experiments prove that the single core cable with copper wire and steel wire armored isolation structure can reduce the current carrying capacity of cables (Note: low water cable not on the table), but because the steel wire armored cable can withstand large tensile stress, the application is still very wide.